There is not a universal fire-extinguishing agent and consequently there is a risk
that using particular types of fire extinguishers on ignited materials or liquids
may result in worsening the fire situation. Under the British Standard EN-2 (Classification
of Fires), fires have been divided into broad classifications for extinguishing
purposes.
The RRFSO Article 13 states where necessary, the Responsible Person
must ensure that:
- the premises are, to the extent that it is appropriate, equipped with appropriate
fire-fighting equipment; and
- any non-automatic fire-fighting equipment so provided is easily accessible, simple
to use and indicated by signs.
Additionally, Article 17 states where necessary, the Responsible
Person must ensure that:
- the premises and any facilities, equipment and devices provided in respect of the
premises ... are subject to a suitable system of maintenance and are maintained
in an efficient state, in efficient working order and in good repair.
Fire Fighting Equipment Checklist
- Are extinguishers suitable for purpose?
- Are there enough extinguishers sited throughout the premises at appropriate locations?
- Are extinguishers visible or does there position need indicating?
- Are the right types of extinguishers located close to the fire hazard and can the
users get to them without exposing themselves to risk?
- Have steps been taken to prevent the misuse of extinguishers?
Minimum Level of Cover
The details stated below are generalised for a simple low risk premises. It does
not consider spare extinguishers or areas of higher fire risk. For such areas expert
advice should be sought. The following list provides a list of salient points that
are generally relevant for all extinguisher types:
- Normally, extinguishers should be sited where persons following an escape route
will readily see them, such as; near to storey exits, along corridors, etc;
- There should be no point in the building that is further than 30m away from an suitable
extinghuisher;
- Extinguishers should be appropriately mounted, with other portable fire fighting
equipment and identified by signage;
- All extinguishers should ,ideally be the same method of operation;
- All staff should be trained on operating the installed extinguishers; and
- Sufficient spare extinguishers should be available.
Class A
All solid materials, usually organic origin in nature (i.e. contains compounds of
carbon) and generally produces glowing embers when ignited. Examples include wood,
textiles, curtains, furniture and plastics.
The minimum level of cover for class A fires is all floors within the building to
have at least two class A extinguishers (a minimum rating of 26A). For floors greater
than 400m2 there must be a minimum total class A rating of 0.065xfloor area (m2).
For small single-occupancy buildings, with a total upper floor area (i.e. excluding
the ground floor, basements, etc) of less than 100m2, the minimum total
class A rating required for all of these above-ground floors is 13A10
(but still with the minimum two class A rated extinguishers per floor). This exception
does not include or apply to the ground floor.
Class B
All flammable liquids and solids, which can be further sub-divided into: (1) Non-miscible
with water (i.e. petrol, oils, solvents, paints and waxes); and (2) Polar Liquid
Fires (hydrophilic / miscible with water) including alcohol, methanol, acetone,
propanol and ethanol.
The assessment of cover for a single liquid container in a given room is calculated
via the total surface area of the container and the Table 1. This table gives the
maximum surface area (in m²) for which a given rated extinguisher(s) is (are) suitable.
However, this cover does not include the spillage cover given below.
- In cases where there are multiple containers less than 2m apart, they should be
considered as a single container;
- In cases where there are multiple containers that are more than 2m and less than
20m apart, they should be considered as forming a divided group. The surface area
of the largest single container, the total surface area of the largest undivided
group (as above), or one third of the total surface area of all of the containers,
whichever is the greater, is used to calculate the minimum rating;
- In cases where the containers are more than 20m apart, the containers should be
considered on an individual basis;
- Additional extinguishers should also be supplied to cover the risk from spillage.
The recommended minimum rating = 10×Anticipated Spillage Volume (in litres). Refer
to the British Standard for full details;
- Additional extinguishers should be provided where the liquids have a low fire point,
or are particularly difficult to extinguish; and
- Where high rated extinguishers are installed, additional low rated extinguishers
should be provided and sited near any anticipated points of fire occurrence.
|
|
21B |
34B |
55B |
70B |
89B |
113B |
144B |
183B |
233B |
|
Max are for 1 extingisher(m2) |
0.14 |
0.23 |
0.37 |
0.47 |
0.59 |
0.75 |
0.96 |
1.22 |
1.55 |
|
Diameter (m) |
0.42 |
0.54 |
0.69 |
0.77 |
0.87 |
0.98 |
1.11 |
1.25 |
1.40 |
|
Rectangular (0.5x (m)) |
0.28 |
0.46 |
0.74 |
0.94 |
1.18 |
1.50 |
1.92 |
2.44 |
3.10 |
|
Max area for 2 extinguishers (m2) |
0.26 |
0.42 |
0.69 |
0.88 |
1.11 |
1.41 |
1.80 |
2.29 |
2.91 |
|
Diameter (m) |
0.58 |
0.73 |
0.94 |
1.06 |
1.19 |
1.34 |
1.51 |
1.71 |
1.92 |
|
Rectangular (0.5x (m)) |
0.52 |
0.84 |
1.38 |
1.76 |
2.22 |
2.82 |
3.60 |
4.58 |
5.82 |
|
Max area for 3 extinguishers (m2) |
0.42 |
0.68 |
1.10 |
1.40 |
1.78 |
2.26 |
2.88 |
3.66 |
4.66 |
|
Diameter (m) |
0.73 |
0.93 |
1.18 |
1.34 |
1.51 |
1.70 |
1.91 |
2.16 |
2.44 |
|
Rectangular (0.5x (m)) |
0.84 |
1.36 |
2.20 |
2.80 |
3.56 |
4.52 |
5.76 |
7.32 |
9.32 |
Table 1: Minimum cover for Class B
Class C
Class ‘C’ fires involve natural mains gas, liquid petroleum gases (e.g. LPG – butane
and propane) and medical or industrial gases.
In all but some very exceptional cases, a gas leak should only be dealt with by
closing a control valve or plugging the leak - personnel should not be encouraged
to tackle these risks in any other way. Refer to the standard for details.
Class D
Class ‘D’ fires involve metals.
It is not possible to make general recommendations for the provision of extinguishers
to protect against combustible metals (e.g. magnesium). Decisions should be made
solely by experts on a case-by-case basis. The use of inappropriate equipment can
make a situation far worse.
Electrical Fires
Electrical fires are not considered to constitute a fire class on their own, as
electricity is a source of ignition that will feed the fire until removed. When
the electricity supply has been isolated, the fire can generally be treated as a
‘Class A’ for extinguishing purposes.
Class F
This is a new class that specifically deals with high temperature (≥ 360°C) cooking
oils used in large industrial catering kitchens, restaurants and takeaway establishments.
Cooking oil fires, because of their auto-ignition temperature, are difficult to
extinguish.
|
Class F Risk |
Cover Required |
|
Surface Area < 0.11m2 |
One 75F extinguisher |
|
Surface Area < 0.4m2 |
Two 75F extinguishers |
|
Surface Area > 0.4m2 |
Fixed system is required |
Table 2: Minimum cover for Class F
As with Class B above, the provision of cover for Class F risks is also a specialist
subject. However, there are two pertinent points: (1) all deep fat frying situations
should be covered (see Table 2) and (2) other fat and cooking oil risks may also
require the provision of either Class F extinguisher(s)16 or a fixed system.
References
- Regulatory
Reform (Fire Safety) Order 2005, SI 2005/1541. The Stationery Office, 2005.
-
The Health and Safety (Safety Signs and Signals) Regulations 1996 .
- BS 5306-8:2000 Fire extinguishing installations and equipment on premises. Selection
and installation of portable fire extinguishers. Code of practice
- BS 5499-1:2002 Graphical symbols and signs. Safety signs, including fire safety
signs. Specification for geometric shapes, colours and layout.
-
Fire Safety Guides. Department for Communities and Local Government Publications,
2006.