Fire detection zones are essentially a convenient way of dividing up a building
to assist in quickly locating the position of a fire. The zone boundaries are not
physical features of the building, although it is normal to make the zone boundary
coincide with walls, floors and specifically fire compartments.
The RRFSO Article 13 states that for fire detection, the Responsible
Person must:
- Where necessary (whether due to the features of the premises, the activity carried
on there, any hazard present or any other relevant circumstances) in order to safeguard
the safety of relevant persons, the responsible person must ensure that the premises
are, to the extent that it is appropriate, equipped with appropriate fire detectors
and alarms;
- For the purposes of paragraph (1) what is appropriate is to be determined having
regard to the dimensions and use of the premises, the equipment contained on the
premises, the physical and chemical properties of the substances likely to be present
and the maximum number of persons who may be present at any one time.
Fire Detection and Warning Checklist
- Can the means of detection ensure a fire is discovered quickly enough for the alarm
to be raised in time for occupants to escape safely?
- Are the detectors of the right type and in the appropriate locations?
- Can the means of warning be heard and understood by everyone throughout the premises?
- Are there provisions for people where the alarm cannot be heard?
- If the fire detection and warning system is electrically powered, does it have a
back-up power supply?
Detection Zone
The size and position of the detection zones will therefore tend to be dependent
on the shape of the buildings, but will also depend on what the building is used
for and to some extent the number of people the building is expected to contain
at any one time. BS 5839-1 has some specific recommendations with respect to detection
zones:
- Unless the total floor area is less than 300m2, zones should be restricted to single
floors;
- If in the same fire compartment, voids of a room may be included in the same zone;
- Zones should not be larger than 2000m² except for manual systems in single storey
open plan buildings, such as a warehouse, where up to 10000m² is allowed;
- Fire detectors in an enclosed stairwell, lift shaft, etc should be considered as
a separate zone;
- The search distance within a zone should be less than 60m (all possible entrance
points must be considered). The search distance only relates to the distance from
entering a zone to being able to determine the location of the fire, it is not necessary
to travel to the fire; and
- Zones should not cross fire compartments, a fire compartment can contain several
zones but a zone should not contain more than one fire compartment.
Alarm Zone
For complex buildings where it is necessary to operate alarm devices differently,
i.e. phased evacuation, then the building should be divided into alarm zones such
that all of the alarm devices in one alarm zone operate in the same way. BS5839-1
contains recommendations for alarm zones:
- The boundaries of all alarm zones should comprise fire-resisting construction;
- Signal overlap between alarm zones should not cause confusion; and
- The same alarm and alert signals should be used throughout a building;
Selection of Appropriate Automatic Detectors
BS5839-1 lists eight categories of cover (see Table 1), depending on what is required.
The category system is a simple short hand method of informing all parties of the
system objectives.
Optical smoke detectors are suitable for most applications giving the fastest response
to slow burning fires - the most common start to fire events. Ionisation detectors
have a quicker response to fast burning fires but an inferior response to slow smouldering
fires. Ionisation detectors are also less acceptable from an environmental point
of view due to the radioactive material that they contain.
BS5839 section 21.1.8 (d) recommends the use of optical detectors to provide coverage
for escape routes due to their superior ability to detect optically dense smoke
that would easily obstruct the use of escape routes.
Opto-heat detectors have been developed to mimic the response of ionisation detectors
to fast burning clean fires yet maintain the advantage of photoelectric detectors
when detecting smouldering fires and allow a higher alarm threshold within the EN54-7
specification under normal conditions thus providing a greater rejection of false
alarms.
Heat detectors should be used in environments where the ambient conditions might
cause false alarms if smoke detection were to be used, for example where there is
a high level of dust, fumes, steam or smoke under normal conditions. There are three
available types of conventional heat detector, a fixed high temperature (triggers
at 92°C), a medium fixed temperature (triggers at 77°C) and a rate of rise heat
detector.
The rate of rise type is the most sensitive type of heat detector, particularly
in areas where the ambient temperature can reach low levels. In order to avoid false
alarms rate of rise detectors should not be used in areas subject to frequent temperature
swings, such as in kitchens, boiler rooms and warehouses with large doors to open
air.
Positioning of Automatic Detectors
The general rules for spacing between any point in a protected area and the detector
nearest to that point should not exceed 7.5m for a smoke detector and 5.3m for a
heat detector. However, to ensure that coverage is provided into the corners of
rooms and no gap is left at the junction point of multiple detectors; spacing’s
have to be reduced. Thus, for a complete coverage of square layouts, spacing’s between
detectors and walls should be reduced to 5m for a smoke detector and 3.5m for a
heat detector, as in Figure 1.
For corridors less than 2m wide only the centre line need be considered therefore
it is not necessary to reduce detector spacing’s in order to provide complete coverage.
Therefore for smoke detectors spacing becomes 7.5m from a wall and 15.0m between
detectors. For heat detectors the spacing becomes 5.3m to a wall and 10.6m between
detectors.
The above data is based on flat level ceilings; for pitched ceilings a detector
should be mounted near (600mm for smoke and 150mm for heat) to the apex but spacing
can be increased by 1% for each 1° of slope up to 25%. Under all normal circumstances
point type fire detectors should be mounted on the ceiling - this ensures that the
height restrictions are met together with the Table 2.
Manual Call Points
Manual call points should be located on escape routes, at all exits to free air
and at all exits from each level of multi-storey buildings.
For general applications, call points should be located such that nobody need to
travel more than 45m to reach the nearest call point. If users have limited mobility
and these users are likely to be the first to operate the alarm or the area is high
risk the distance should be reduced to 25m.
Call points should be located near to specific hazards (e.g. flammable liquid store)
and at 1.4m (+/- 0.2m) from the floor in well lit easily accessible positions. Lower
mounting heights might be needed to accommodate users in wheel chairs.
References
- Regulatory
Reform (Fire Safety) Order 2005, SI 2005/1541. The Stationery Office, 2005.
- BS 5839-1:2002 Fire detection and fire alarm systems for buildings. Code of practice
for system design, installation, commissioning and maintenance.
- The Building Regulations 2000: Approved Document B fire safety.
The Stationery Office.
-
Fire Safety Guides. Department for Communities and Local Government Publications,
2006.